High environmentally friendly water heater & air conditioner & heat pump |
Model | MG-030KFGRS | MG-030KFGRS/380 | MG-050KFGRS | MG-10KFGRS |
Standard components | Cabinet/color | spray coating |
Refrigerant | R134A |
Power supply | 220V~240V/50Hz/1ph | 380V~415V/50Hz/3ph |
Compressor type | Copeland EVI compressor |
Compressor model / quantity | ZW30KSE*1 | ZW34KSE*1 | ZW61KSE*1 | ZW61KSE*2 |
Condenser | high efficiency shell and tube heat exchanger |
Economy unit | plate heat exchanger |
Evaporator | blue hydrophilic aliuminium foil,wavy fin and copper tube heat exchanger |
Throttle unit | heat expansion valve |
A/C contactor | |
Thermal relay | |
Controller | Muti-function controller |
Protection function | | Tempreature protection, time protection, water flow protection, antifreeze protection, current protection |
Water pressure switch | | 0.015Mpa :OFF, 0.03Mpa: ON |
Low pressure switch | 0.05/0.15MPa |
High pressure switch | 3.0/3.4MPa |
Power supply line size | 2.5mm2 | 2.5mm2 | 4mm2 | 6mm2 |
Package | W*D*H | 900*500*1220 | 900*500*1220 | 1150*510*1420 | 1540*820*1320 |
Specifications | Heating capacity(A/20ºC) | kW | 7.4 | 8.3 | 13.8 | 27.6 |
Input power when heating | kW | 2.9 | 3.3 | 5.4 | 10.8 |
COP | kW/kW | 2.55 | 2.52 | 2.56 | 2.56 |
Rated outlet water temp | ºC | 70 |
Max outlet water temp | ºC | 75 |
Water flow | m3/H | 2.2 | 2.5 | 4.1 | 8.1 |
Level of protection | | IPX4 | IPX4 | IPX4 | IPX4 |
Electric shock proof grade | | I | I | I | I |
Noise | dB(A) | ≤55 | ≤55 | ≤58 | ≤66 |
Net weight | kg | 112 | 112 | 164 | 320 |
Gross weight | kg | 118 | 118 | 174 | 333 |
Dimension | W*D*H | 830*490*1160 | 1110*490*1260 | 1450*740*1150 |
Pipe size | mm | DN25 | DN25 | DN25 | DN32 |
Working mode | | Heating mode |
Remarks: |
Working air temperature range:5ºC to 43ºC |
Rated working condition: Heating: air temperature (DB/WB): 20ºC/15ºC, Initial water temperature: 15ºC, final water temperature: 70ºC or 75ºC. |