Model | MGKH-100II | MGKH-120II | MGKH-150II | MGKH-200II | MGKH-250II | MGKH-300II | |
Heating capicity (1) | kw | 30.4 | 34.8 | 42.4 | 60.5 | 71.5 | 90.2 |
Input power | kw | 9.55 | 10.89 | 13.32 | 18.81 | 22.32 | 28.05 |
Current | A | 19.1 | 21.8 | 26.6 | 37.6 | 44.6 | 56.1 |
COP | 3.18 | 3.19 | 3.18 | 3.22 | 3.20 | 3.22 | |
Hot water supply | L/H | 522 | 598 | 728 | 1040 | 1230 | 1551 |
Heating capicity (2) | kw | 27.6 | 31.6 | 38.5 | 55 | 65 | 82 |
Input power | kw | 10.42 | 11.88 | 14.53 | 20.52 | 24.34 | 30.60 |
Current | A | 20.8 | 23.7 | 29.0 | 41.0 | 48.7 | 61.2 |
COP | 2.65 | 2.66 | 2.65 | 2.68 | 2.67 | 2.68 | |
Hot water supply | L/H | 396 | 453 | 552 | 788 | 931 | 1175 |
Voltage | V/Hz | 380~415/50/3 | |||||
Rated/Max water temp | 75~80 °C | ||||||
Refrigeration | R134A | ||||||
Compressor(Copeland Scroll) | ZW61KAE*2 | ZW72KAE*2 | ZW79KAE*2 | ZW108KAE*2 | VR144KSE*2 | ZW108KAE*3 | |
Condenser (Tank HE) | 155HD-065*2 | 155HD-065*2 | 155HD-065*2 | Tube-in Shell heat exchanger | |||
Ambient temperature | (5 °C -- 45 °C) | ||||||
Water pipe size | DN40 | DN40 | DN40 | DN50 | DN65 | DN80 | |
Dimension | mm | 1450*740*1150 | 1507*857*1611 | 1507*857*1611 | 1850*1000*1950 | 2000*1100*2080 | 2200*1100*2080 |
Weight (N./W.) | kg | 280/300 | 320/340 | 372/395 | 560/588 | 582/615 | 680/720 |
Function:
1. Max outlet water temperature 75°C.
2. Compressor over current protection function
3. Automatically remember all parameters if power off
4. Display water tank temp, preset temp and inquiry function
5. Turn on/off at two certain period of time within 24 hours.
6. Compressors run in balance and starts are staggered.
7. Electric heating back up.
8. Automatically and forced defrosting function
9. Huge LCD display (with blue background and white word).
10. Perfect protect and display
11. Lack of phase or wrong phase of three phase power supply can be protected.
12. Anti-freezing function
13. Under the condition of without control panel (or panel damaged), system can work automatically.
Temperature:
1.Working temperature range of outdoor: 5°C to 43°C
2.Rated working condition: Rated working condition: dry-bulb temp: 20 °C, wet-bulb temp: 15°C, cool water temp: 15°C, hot water temp:70 °C.
3.Max water temperature: 75°C
Some important information:
1. Working mode: Heating mode
2. Level of protection: IPX4
3. Electric shock proof grade: I
4. Refrigerant: R134A
5. No electric heater back up
Suppliers with verified business licenses