Customization: | Available |
---|---|
Energy Efficiency Grade: | One |
Heat Temperature: | 80°c |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Function:
1. Max outlet water temperature 75°C.
2. Compressor over current protection function
3. Automatically remember all parameters if power off
4. Display water tank temp, preset temp and inquiry function
5. Turn on/off at two certain period of time within 24 hours.
6. Compressors run in balance and starts are staggered.
7. Electric heating back up.
8. Automatically and forced defrosting function
9. Huge LCD display (with blue background and white word).
10. Perfect protect and display
11. Lack of phase or wrong phase of three phase power supply can be protected.
12. Anti-freezing function
13. Under the condition of without control panel (or panel damaged), system can work automatically.
Temperature:
1.Working temperature range of outdoor: 5°C to 43°C
2.Rated working condition: Rated working condition: dry-bulb temp: 20 °C, wet-bulb temp: 15°C, cool water temp: 15°C, hot water temp:70 °C.
3.Max water temperature: 75°C
Some important information:
1. Working mode: Heating mode
2. Level of protection: IPX4
3. Electric shock proof grade: I
4. Refrigerant: R134A
5. No electric heater back up
Model | MGKH-100II | MGKH-120II | MGKH-150II | MGKH-200II | MGKH-250II | MGKH-300II | |
Heating capicity (1) | kw | 30.4 | 34.8 | 42.4 | 60.5 | 71.5 | 90.2 |
Input power | kw | 9.55 | 10.89 | 13.32 | 18.81 | 22.32 | 28.05 |
Current | A | 19.1 | 21.8 | 26.6 | 37.6 | 44.6 | 56.1 |
COP | 3.18 | 3.19 | 3.18 | 3.22 | 3.20 | 3.22 | |
Hot water supply | L/H | 522 | 598 | 728 | 1040 | 1230 | 1551 |
Heating capicity (2) | kw | 27.6 | 31.6 | 38.5 | 55 | 65 | 82 |
Input power | kw | 10.42 | 11.88 | 14.53 | 20.52 | 24.34 | 30.60 |
Current | A | 20.8 | 23.7 | 29.0 | 41.0 | 48.7 | 61.2 |
COP | 2.65 | 2.66 | 2.65 | 2.68 | 2.67 | 2.68 | |
Hot water supply | L/H | 396 | 453 | 552 | 788 | 931 | 1175 |
Voltage | V/Hz | 380~415/50/3 | |||||
Rated/Max water temp | 75~80 °C | ||||||
Water flow | m3/H | 6.8 | 7.8 | 9.5 | 13.5 | 16.0 | 20.1 |
Water pressure drop | kPa | ≤60 | ≤68 | ≤70 | ≤72 | ≤75 | ≤85 |
Refrigeration | R134A | ||||||
Inverter Compressor(Copeland Scroll) | ZW61KAE*2 | ZW72KAE*2 | ZW79KAE*2 | ZW108KAE*2 | VR144KSE*2 | ZW108KAE*3 | |
Condenser (Tank HE) | 155HD-065*2 | 155HD-065*2 | 155HD-065*2 | Tube-in Shell heat exchanger | |||
Evaporator | Blue Finned heat exchanger | ||||||
4-way valve | SanHua Brand 4-way valve | ||||||
Throttle unit | Danfoss electronic expansion valve | ||||||
Controller | LCD wire controller | ||||||
Ambient temperature | (5 °C -- 45 °C) | ||||||
Water pipe size | DN40 | DN40 | DN40 | DN50 | DN65 | DN80 | |
Noise | ≤66 | ≤66 | ≤68 | ≤70 | ≤72 | ≤76 | |
Dimension | mm | 1450*740*1150 | 1507*857*1611 | 1507*857*1611 | 1850*1000*1950 | 2000*1100*2080 | 2200*1100*2080 |
Weight (N./W.) | kg | 280/300 | 320/340 | 372/395 | 560/588 | 582/615 | 680/720 |
Heating testing condition 1 : air temperature (DB/WB): 30ºC/26ºC, water temperature (inlet/outlet):30ºC/80ºC. | |||||||
Heating testing condition 1 : air temperature (DB/WB): 20ºC/15ºC, water temperature (inlet/outlet):15ºC/75ºC. |